What if I add a signal isolator differential pressure transmitter to zero drift?
Time:2018-07-12 Hits:483
Whenever the project enters the commissioning phase, we will always encounter various problems. For example, the signal isolator has been added but the zero drift of the differential pressure transmitter is still serious, eliminating the possibility of on-site interference. In order to check the reasons from the following aspects.
If there are multiple zero differential pressure transmitters with severe zero drift and some regular fluctuations in time intervals, the main reasons for this situation are as follows:
(1) Product quality problems of the transmitter itself;
(2) The pressure guiding pipeline is not smooth;
(3) the effect of temperature;
(4) The influence of mechanical displacement.
In order to determine the cause of the problem, we only have to investigate one by one. First, we need to check the pressure guiding pipeline to detect the presence of stress. If it is found that there is a large stress, it is necessary to carry out the stress relief work. Secondly, check whether the transmitter is installed firmly. Because the transmitter is not installed firmly, it will cause mechanical displacement, which will cause the transmitter to drift at zero point. Therefore, it is necessary to check the installation of the transmitter and carefully check whether the transmitter brackets are installed firmly. If some transmitter brackets are found to be not securely installed, the transmitter must be tightened. At this time, the fault can be basically eliminated.